installedgenerator

Generator size calculator: what your house needs in kW

Tick what must run; the calculator adds the running watts and the largest starting surge, then names the size.

Checked November 17, 2026By the installedgenerator.com desk

Generator size calculator

Tick what should keep running in an outage and pick the fuel at the house. The plate that clears your peak is the size to quote. It sizes home standby units (10 to 28 kW); for a portable, see portable vs standby.

Fuel at the house
Keep the house safe
Kitchen and laundry
Large electric loads

Recommended plate

10 kW

Rated 9 kW on natural gas; covers a peak of 5,100 W.

  1. 10kW

    Recommended

    Propane
    10kW
    Natural gas
    9kW
    Model
    Generac 7257
    Installed
    $3,650 to $10,600
  2. 14kW

    Propane
    14kW
    Natural gas
    14kW
    Model
    Generac 7258
    Installed
    $5,000 to $16,200
  3. 18kW

    Propane
    18kW
    Natural gas
    17kW
    Model
    Generac 7259
    Installed
    $5,000 to $16,200
  4. 22kW

    Propane
    22kW
    Natural gas
    21kW
    Model
    Generac 7260
    Installed
    $7,600 to $25,400
  5. 24kW

    Propane
    24kW
    Natural gas
    22.5kW
    Model
    Generac 7261
    Installed
    $7,600 to $25,400
  6. 26kW

    Propane
    26kW
    Natural gas
    24kW
    Model
    Generac 7327
    Installed
    $7,600 to $25,400
  7. 28kW

    Propane
    28kW
    Natural gas
    25kW
    Model
    Generac 7282
    Installed
    $7,600 to $25,400
Every gauge runs on one 0 to 28 kW scale at the rating for your fuel; the black tick is your peak. Ratings from Generac's spec sheets. Installed ranges by size band (7 to 10, 12 to 20, 22 to 30 kW) from ConsumerAffairs, updated Sep 23, 2026.
Running wattseverything ticked, at the same time
2,900W
Extra watts while the largest motor startsRefrigerator: 2,900 W starting minus 700 W running
2,200W
Peak to cover
5,100W

Generac 10 kW: $3,699 for the unit, $4,329 with a 100 A transfer switch (Norwall, read Nov 11, 2026). Installed totals add the pad, fuel line, wiring, permit and labor. Installed cost by size

The helper adds the running watts of everything ticked, adds the largest single motor's extra starting watts on top (motors start one at a time), and names the smallest standard air-cooled size whose rating on your fuel covers that peak. Wattages are typical figures from manufacturers' charts; the nameplate on your own appliance is the better number. An installer confirms the size before quoting. How the calculator works.

The generator size calculator above shows its arithmetic line by line: the running watts, the extra watts while the largest motor starts, the peak and the size that covers it.

How the calculator works

The generator size comes from three steps: add the running watts of everything that may run at the same time, add the single largest starting surge on top because motors start one at a time, then take the smallest standard size whose rating on your fuel covers that peak. The calculator above does exactly that:

  1. Running watts. It adds the running watts of every load you tick.
  2. Largest starting surge. It adds the largest single extra while starting (starting minus running watts), once.
  3. Size. It names the smallest of Generac's air-cooled sizes (10, 14, 18, 22, 24, 26 and 28 kW) rated at least that peak on your fuel.

The method is the one Champion and Briggs & Stratton publish, whose charts list starting watts as the extra a motor draws while it starts: add the running watts, then add the largest single extra on top. Generac writes its formula as the running total plus the highest single starting wattage, which counts that motor's running watts twice and gives a larger peak (16,100 W instead of 12,500 W for the worked example below, an 18 kW unit), and it says starting watts are often two to three times the running figure (page dated Aug 9, 2026); an installer may size that way. Briggs & Stratton calls the initial surge key to right-sizing (all read November 17, 2026).

The result is a first estimate; every wattage and its source is listed in how the cost figures and the sizing helper are worked out (checked November 11, 2026).

Running watts and starting watts

Running watts are what an appliance draws while it works; starting watts are what a motor draws for a moment while it starts, and Generac says that figure is often two to three times the running one (read November 17, 2026).

Appliance Running watts Starting watts Extra while starting
Refrigerator 700 2,900 2,200
Furnace blower, 1/2 hp 600 1,500 900
Sump pump, 1/2 hp 600 1,500 900
Lights 600 600 0
Computer and router 400 400 0
Central air, 3 ton 3,600 9,600 6,000

Sources: Generac's wattage worksheet (refrigerator running, lights, computer and router), Champion's wattage chart (refrigerator starting), Kohler's motor table (furnace blower, sump pump) and one dealer chart, Portlandia Electric Supply (central air), as recorded in the calculator's data file, checked November 11, 2026 (central air corrected November 17, 2026). The last column is starting minus running, the surge the calculator adds. Makers' charts disagree; the calculator uses its data file's figure.

The 3-ton row comes from that one dealer chart, whose surge column is labelled as additional watts, so the calculator adds its 6,000 W to the 3,600 W running figure. That is the cautious reading: Champion lists a 3-ton unit at 3,000 to 3,500 W running with 5,000 to 6,000 W of extra starting watts (read November 18, 2026), a peak of 8,000 to 9,500 W, close to the calculator's 9,600 W. A compressor without a soft-start kit can draw far more: Generac puts a 3-ton unit at about 3,500 to 5,000 W running and up to 15,000 to 18,000 W starting (read November 17, 2026). The calculator can therefore name a size too small for a hard-starting compressor, and the installer checks yours.

A worked example with central air

The five loads the calculator ticks by default (refrigerator, furnace blower, sump pump, lights, computer and router) plus a 3-ton central air unit add up to 6,500 running watts; the largest starting surge is the air conditioner's extra 6,000 W, so the peak is 12,500 W and the calculator names a 14 kW unit on natural gas or propane.

Loads running together Running sum Largest starting surge Peak Natural gas pick Propane pick
Refrigerator, furnace blower, sump pump, lights, computer and router, central air 3 ton 6,500 W 6,000 W (central air) 12,500 W 14 kW (rated 14 kW) 14 kW (rated 14 kW)
The same five loads with central air 2 ton 5,400 W 4,500 W (central air) 9,900 W 14 kW (rated 14 kW) 10 kW (rated 10 kW)

Source: wattages from the calculator's data file (checked November 11, 2026; central air corrected November 17, 2026), the 2-ton row from the same dealer chart at 2,500 W running plus 4,500 W while starting; ratings from Generac's spec sheets Rev. D 08/13/2026 (10 to 18 kW); the calculator's arithmetic below.

Running: 700 + 600 + 600 + 600 + 400 + 3,600 = 6,500 W. Largest extra while starting: the central air's 6,000 W (refrigerator 2,200, furnace blower and sump pump 900 each, lights and the computer 0). Peak: 6,500 + 6,000 = 12,500 W, above the 10 kW unit's rating on either fuel, so the 14 kW unit, rated 14,000 W on both, is the pick.

With a 2-ton unit instead, the running sum is 5,400 W and the largest surge 4,500 W, a peak of 9,900 W. A 10 kW propane rating covers that and a 9 kW natural gas rating does not, so the natural gas pick jumps to 14 kW. Both rows use the data file's wattages; neither is a measured household or a quote.

Why natural gas and propane give different sizes

The same unit is rated lower on natural gas than on propane, so a peak that fits a propane rating can need the next size up on natural gas, and the calculator asks for the fuel before it picks.

Size Rated on propane Rated on natural gas
10 kW 10 kW 9 kW
14 kW 14 kW 14 kW
18 kW 18 kW 17 kW
22 kW 22 kW 21 kW
24 kW 24 kW 22.5 kW
26 kW 26 kW 24 kW
28 kW 28 kW 25 kW

Source: Generac spec sheets Rev. D 08/13/2026 (10 to 18 kW and 22 to 28 kW), as recorded in the calculator's data file, checked November 11, 2026. Other makers' ratings differ a little; the calculator uses Generac's air-cooled line.

The 10 kW is rated 9 kW on natural gas on its spec sheet and 10 kW on Generac's product page, and the calculator uses the lower figure. Some sellers still print older Guardian-series sheets that rate the 22, 24 and 26 kW at 19.5, 21 and 22.5 kW on natural gas, hence those figures on some seller pages. Fuel use, tank size and fuel cost are compared in natural gas vs propane for a standby generator.

Whole house or essential circuits

Whole-house means the generator carries every circuit the transfer switch serves; essential circuits means the refrigerator, lighting, well pump and a handful of critical outlets, per Generac, and a smaller unit can serve a large home when load management shuts big loads off; Kohler says its load shed kit allows the use of a smaller generator set (both read November 17, 2026).

Publisher Home or case Size it names Condition it states Read
Generac 2,000 sq ft home 18 to 22 kW With load management; square footage is only a starting point Nov 17, 2026
Generac 1,550 sq ft home 10 to 14 kW (18 kW with a heat pump or high-draw medical equipment) With one or two load managers, essential circuits Nov 17, 2026
Kohler Mid-sized home wanting most major systems, including central air 14 to 20 kW A general guideline, not a calculation Nov 17, 2026

Sources: Generac's sizing guide (page dated Aug 9, 2026) and Kohler's sizing page (no date shown), both read November 17, 2026. Each range is that publisher's own claim, not a rule of this site.

Generac also says two neighbors with identical floor plans could need generators 8 kW or more apart, which is why the calculator sizes from loads, not square feet.

What an installer's load calculation adds

Generac says to have a professional complete a load analysis for your home and Kohler calls a professional load assessment the most accurate way to determine the right generator size, so the calculator is a first estimate and an installer's number can differ from it. Kohler's sizing page also points owners to a professional site survey of the electrical load (all read November 17, 2026).

As Schneider Electric explains the 2023 National Electrical Code (post dated July 7, 2025), section 702.4(A)(2)(a) requires a backup source connected automatically to supply the entire load connected to it, and 702.4(A)(2)(b) lets an energy management system limit that to the maximum load the system will permit. The North Carolina Office of State Fire Marshal, quoting NFPA Code Making Panel 13, says the NEC prohibits an optional standby installation that will transfer automatically to more load than it can supply (interpretation dated December 1, 2024; both read November 17, 2026).

The edition matters. The (A)(2) numbering is the 2023 edition; older editions number the same rule 702.4(B)(2), and the installer works to the edition the local inspector enforces.

The installer, the electrician and the inspector decide what load the system must carry and whether load management is allowed. The calculator can come out smaller than a dealer's number because it counts the loads you tick, while an installer's load calculation counts the load the system will be connected to, and Generac's 8 kW gap between identical floor plans shows how far real homes differ.

kW or kVA on the label

Generac rates its home standby units in kW on its spec sheets, and kVA is the same power before the power factor: kW equals kVA times the power factor. Depco Power Systems, writing about commercial and industrial sets, defines the power factor as kW divided by kVA, so a 750 kVA set at 0.8 gives 600 kW. ANA Corp, writing about jobsite sets, says only about 80 percent of the kVA rating becomes usable output (both read November 17, 2026). Neither covers home units: read the rating on the unit's own spec sheet. The calculator's sizes are in kW, so nothing needs converting.

What the calculator does not do

The calculator names a size from the loads you tick and the wattages in its data file; it does not read your panel, size a transfer switch, check a hard-starting compressor or replace an installer's load calculation.

  • Central air uses one dealer chart; per Generac, a 3-ton compressor without a soft-start kit can draw up to 15,000 to 18,000 W while it starts.
  • The electric range counts one element at a time at 2,000 W (Champion's wattage chart); a whole range with every element on draws more.
  • Sizes come from Generac's air-cooled line only, and above the 28 kW rating on your fuel it names no size.

What a standby unit costs installed is on whole house generator installed cost, and what a dealer quote includes is on Generac generator installed cost. A portable generator is compared with a standby unit in portable vs standby generators; a portable generator is never connected to house wiring without a transfer switch or an approved interlock.

Frequently asked questions

Are generators sized in kW or kVA?

Generac rates its air-cooled home standby units in kW (10 to 28 kW in the calculator's list), so nothing needs converting. kW equals kVA times the power factor, which Depco and ANA Corp put at about 0.8 for the commercial and jobsite sets they sell (read Nov 17, 2026). For a home unit, read the rating on its own spec sheet instead of applying 0.8.

How many kW generator to run a 2000 sq ft house?

Generac says an 18 to 22 kW unit with load management, with 22 kW the standard for whole-home protection (page dated Aug 9, 2026); Kohler's general guideline for a mid-sized home that wants most major systems, including central air, is 14 to 20 kW (both read Nov 17, 2026). The same Generac page also says a 2,000 sq ft house typically needs a 20 or 22 kW unit. Both ranges are those publishers' claims, not a rule of this site. Generac also says identical floor plans can need generators 8 kW or more apart, so the calculator works from the loads and an installer's load calculation confirms the size.

Can a 16kW generator run a house?

It depends on the loads: a peak from the calculator at or under that unit's rating on your fuel (natural gas ratings run lower than propane) is covered, and an installer's load calculation decides whether that is the whole house. The calculator's list (Generac's air-cooled 10 to 28 kW line) has no 16 kW size, and ratings differ by maker and fuel, so check that unit's spec sheet. Generac says load management lets a mid-sized unit serve a larger home by shutting big loads off.

Can I run my whole house with a 6500 watt generator?

Not by the calculator's method: its worked example with a 3-ton central air unit and the five default loads peaks at 12,500 W, and the air conditioner alone draws 9,600 W while starting before the other loads are added. A portable of that size can cover a few essentials; a whole house with central air is the job of a standby unit, and Champion lists its whole-house standby generators from 8,500 W up (read Nov 17, 2026). A portable generator is never connected to house wiring without a transfer switch or an approved interlock; Champion says a manual transfer switch installed by a licensed electrician routes generator power to chosen circuits and prevents back-feeding utility lines.